Detail AC Panel ENC-GR2500L-Sus
AC Panel
Mounting type Side-mounting
Cooling capacity(W) 2480
Setting Temperature Range(℃) 25~45
Use Area Temperature(℃) -5~55
Use Area Humidity(%RH) 10~85 (No condensation)
External dimensions(mm) H1450×W450×D150
Weight(kg) 42
Surface finish SUS-HL Finish
Rated Voltage(V) Single-phase AC200~240
Consumption Current: Rated(A) 6.1/5.9
Consumption Current: MAX(A) 6.8/6.6
Consumption wattage: Rated(W) 1000
Consumption wattage: MAX(W) 1100
Recommended breaker capacity (A) 15
Vibration Resistance Equivalent to JIS Z 0200 Level1
Dust prevention / dust proof protection class IPX4 (ENC-SUS unit only), Equivalent to IP54 (internal circulation route)
Refrigerant / Fill ration(g) R1234yf 800g
Noise (dB (A)) Approx. 80
External Output Alarm output (No-voltage/normal open: resistive load 250V 2A), Can be switched to no-voltage/normal close by setting
Display Internal temperature/Error/RUN